Do I need a boiler feed pump, a condensate pump, or both?

Most steam plants need both, working as a set. The condensate return pump gathers condensate as it drains back and lifts it to a feed tank or deaerator; the boiler feed pump then pushes that water into the boiler against full operating pressure. If your only issue is returning condensate to a tank, a condensate unit is enough. If you are feeding the boiler itself, you need a feed pump selected with the available NPSH in mind. We size both together.

Condensate return pumps

As steam gives up its heat it condenses back to hot water, and that condensate has to get back to the boiler side. A condensate return unit is a receiver tank with one or more pumps that collect the returning condensate and send it on to a feed tank or deaerator. Because the water is hot, the pump and seal are selected for the temperature, and the receiver is sized so the pump does not short cycle. Returning condensate saves energy and treated water, so a reliable return set pays back quickly.

Boiler feed pumps

The boiler feed pump does the harder job: it takes water from the feed tank and delivers it into the boiler at boiler pressure, on demand, without ever running the feed water short. Feed water is hot and near its boiling point, so cavitation is the constant risk. Feed pumps are usually multistage centrifugal designs chosen for a low required NPSH, and the feed tank is elevated to give the pump the suction head it needs. Flow is matched to the boiler evaporation rate with margin, and head must clear the operating pressure plus the feed valve differential.

Getting the sizing right

  • NPSH first. Available NPSH must exceed the pump requirement at the hot feed-water temperature, or the pump cavitates. This is the single most important number on a feed pump.
  • Temperature and materials. The pump, mechanical seal, and elastomers all have to be rated for the actual water temperature.
  • Flow with margin. Match feed flow to the boiler evaporation rate plus a margin so the pump never starves the boiler.
  • Head to operating pressure. Size head to the boiler pressure plus piping losses and the feed valve differential.
  • Control scheme. On-off, modulating, or variable speed feed control changes how the pump is selected and how hard it cycles.

Pump lines available through Brabazon

  • Grundfos for multistage feed pumps and packaged systems.
  • Paco for centrifugal feed and condensate duties.
  • Yeomans for industrial pumping service.
  • Barmesa for condensate transfer and general pumping.
  • Power-Flo for general-purpose transfer pumping.

Service and failure considerations

On hot-water pumps the mechanical seal is the usual first casualty, followed by the impeller when cavitation sets in. Low NPSH, a starved feed tank, or water hotter than the pump was rated for all lead to the same symptoms: falling capacity, noise, and rapid seal wear. Keep the feed tank level and temperature within spec, and address seal weep early. When a rebuild is needed, our factory-trained technicians handle boiler feed and condensate pumps through pump repair.

Industries we serve

Boiler feed and condensate pump questions, answered first

What is the difference between a boiler feed pump and a condensate return pump?

A condensate return pump collects condensate as it drains back from the steam system and pumps it to a feed tank or deaerator, while a boiler feed pump takes water from that tank and delivers it into the boiler at boiler pressure. Condensate pumps handle lower pressure and moderate flow; feed pumps must overcome the full boiler operating pressure. In many plants both work together as a boiler feed and condensate return set.

Why does NPSH matter so much on boiler feed pumps?

NPSH matters because feed water is hot and close to its boiling point, so it flashes to vapor easily and cavitates the pump. The available net positive suction head has to exceed what the pump requires, which is why feed tanks sit elevated and feed pumps are chosen with a low required NPSH. Ignore it and the pump cavitates, loses capacity, and destroys its impeller and seals.

What temperature can these pumps handle?

Condensate and boiler feed pumps are built for hot water, but the exact limit depends on the pump and its seal and material selection. Condensate is typically returned hot, and feed water from a deaerator is hotter still. The pump, mechanical seal, and elastomers must all be rated for the actual water temperature, or the seal fails quickly and the pump cavitates as the water flashes.

How do I size a boiler feed pump?

Size the flow to the boiler evaporation rate plus a margin, and size the head to the boiler operating pressure plus piping losses and the required feed valve differential. Then confirm the available NPSH beats the pump requirement at that duty. Getting flow, head, temperature, and NPSH right together is what keeps a feed pump from cavitating or running short of the boiler demand.

Size a feed and condensate set for your boiler

Send us your boiler pressure, evaporation rate, feed-water temperature, and available NPSH and an engineer will size the set and quote it. We answer 24/7.

Request a quote

Tell us your boiler pressure, flow, water temperature, and suction conditions and a pump specialist from your nearest branch will size and quote the pumps. Or call 800.825.3222, answered 24/7.

Request a boiler feed or condensate pump quote

About your facility (optional, helps us better understand your system)

A person from your nearest Brabazon branch follows up, usually within one business day. Urgent? Call 800.825.3222, answered 24/7.